Energy saving analysis using burner /thermal tank and heater electric in the marine fuel oil (mfo) treatment process

Siska Ayu Kartika, N.H. Abdullah, P. Saksono

Abstract


Energy savings in Diesel Power Plants (PLTD) have been carried out by comparing the Marine Fuel Oil (MFO) processing process when using a burner/thermal tank and an electric heater. Energy savings are analyzed in this study by calculating the comparison of operational costs, cost efficiency and processing time. The place of research was carried out in one of the Diesel Power Plants in Indonesia, with the object of research being an electric heater and a burner/thermal tank. The research method used quantitative methods in the form of literature study, observation, and field testing. The research was conducted by collecting data on temperature, humidity, and fuel consumption when testing the MFO treatment every 1 hour until the specified temperature was reached 94-96°C. Based on the research results, the processing of MFO using a burner/thermal tank is more efficient in terms of time at the beginning of processing, with a savings of 17.2% and in terms of operational costs more efficient 11.67%. However, after the process continued for 7 days, MFO processing using an electric heater was more efficient in terms of operating costs by 31.87%.


Keywords


heater electric; burner/thermal tank; efficiency; energy saving

Full Text:

PDF

References


Hasna, H. S. 2019. The Process of Treatment Marine Fuel Oil (MFO) As Fuel In Diesel Engines. Journal of Chemical Engineering State University Semarang. Thesis is not published. Semarang.

Imam, K. 2015. Utilization of Alternative Energy as Energy Renewed To Support Fuel Substitution. University Engineering Journal Wijaya Putra. Thesis is not published. Surabaya.

L. Edward, Sunardi. 2014. Comparison of Energy Prices from Energy Sources New Renewable And Fossil. Center for the Study of Nuclear Energy Systems. Report unpublished research. Jakarta.

Holman, Jack P. 2010. Heat Transfer: Tenth Edition. New York: Mac Graw Hill.

Cengel, Yunus A., 2003. “Heat Transfer: A Practical Approach Second Edition," McGraw-Hill. New York.

Manual book Thermal Oil Heater. PT Mubarok Pratama.

Mulyamah. 1987. Change management. Jakarta: Yudhisthira.

Specification for MFO Type of Fuel Oil (Directorate General of Oil and Gas, 2008).

Complete Basic Physics Formulas (Wikibooks).

Concession Data of PT PLN (Persero) PLTD Gunung Malang.

Anandh N. and P. Kumar. 2021. ”A Case Analysis on Energy Savings and Efficiency Improvement of a Chiller Plant in a Luxury Hotel Building”, International Energy Journal 21: 447 – 456.

Shaari M.S., Mariadas P.A, Hussain N.E.,Murthy U. 2021. “The Effect of Energy Consumption in the Agricultural Sector on CO2 Emission in Malaysia”. International Energy Journal 21: 427 – 436.

Upakool J., Thanarak P. 2021. “Monitoring and Assessment of Energy Efficiency and CO2 Emission from Cogeneration Power Plants”. International Energy Journal 21: 323 – 338.

Win T., Harayanto T., Sari D.W. 2021. “Analysis of Energy Efficiency of Indonesia’s Sugar Industry”. ”. International Energy Journal 21: 245 – 256.




DOI: https://doi.org/10.24853/sintek.17.1.7-16

Refbacks

  • There are currently no refbacks.


Copyright (c) 2023 SINTEK JURNAL: Jurnal Ilmiah Teknik Mesin

Powered by Puskom-UMJ