ANALISIS KINERJA EVAPORATOR PADA VAPORS COMPRESSION REFRIGERATION SYSTEM MENGGUNAKAN REFRIGERANT R410A

Sukarman Sukarman, Khoirudin Khoirudin, Murtalim Murtalim, Ahmad Fauzi, Ricko Valderama, Amri Abdulah, Anwar Ilmar Ramadhan

Abstract


VCR system  is an energy conversion device that uses a mechanical vapour compression cycle in the process. The performance of the VCR system using environmentally friendly refrigerants is a significant issue, and much research is still underway to evaluate and improve the efficiency of the systems used. Therefore, this paper presents an experimental investigation of the performance of the refrigeration cycle. A VCR system was used as a test tool. The coefficient of performance (CoP) was studied using a VCR system  design with varying evaporator loads. Variation of an evaporator load is done by intervening fan rpm at five rpm levels. The VCR system uses a compressor with a capacity of 365 watts using R410A refrigerant. Refrigerant R410A is one of the alternative refrigerants to replace R22 which is not environmentally friendly. Experimental data was validated using Genetron Properties 1.1 software. Experimental analysis data showed that the highest CoP was obtained at the lowest rpm with a value of 3.17. Meanwhile, the lowest CoP is 3.02, obtained at the highest rpm. Loading the evaporator with fan rpm produces a CoP value indirectly proportional to the fan rpm value. Genetron 1.1 software validation results produce a higher CoP value of about 2%-3% than experimental data.


Keywords


Coeficient of performance, Evaporator, Genetron properties 1.1, Refrigerant R410A, VCR-system.

Full Text:

PDF

References


Al-Rashed, Abdullah A.A.A. 2011. “Effect of Evaporator Temperature on Vapor Compression Refrigeration System.” Alexandria Engineering Journal 50(4): 283–90. http://dx.doi.org/10.1016/j.aej.2010.08.003.

Aprea, Ciro, and Angelo Maiorino. 2011. “An Experimental Investigation of the Global Environmental Impact of the R22 Retrofit with R422D.” Energy 36(2): 1161–70. http://dx.doi.org/10.1016/j.energy.2010.11.032.

ASHRAE. 2013. ASHRAE Handbook: Fundamentals. Atlanta: ASHRAE: Atlanta, GA, USA.

Azmi, W. H. et al. 2017. “Potential of Nanorefrigerant and Nanolubricant on Energy Saving in Refrigeration System – A Review.” Renewable and Sustainable Energy Reviews 69(October 2016): 415–28. http://dx.doi.org/10.1016/j.rser.2016.11.207.

Chemours Company. 2019. 3 Freon TM 410A Thermodynamic Properties (SI Units).

Dwinanto, Matheus M, and Suhanan Prajitno. 2018. “Optimization of a Dual-Evaporator Vapor Compression Refrigerator.” In , 181–87.

Environmental Protection Agency. 2016. Federal Register. USA: https://www.govinfo.gov/content/pkg/FR-2016-04-18/pdf/2016-08163.pdf.

K. Wang, Shan. Air-Conditioning and Refrigeration Mechanical Engineering Handbook.

Kim, Minsung et al. 2009. “Performance of a Residential Heat Pump Operating in the Cooling Mode with Single Faults Imposed.” Applied Thermal Engineering 29(4): 770–78.

Ramadhan, Anwar Ilmar, Wan Hamzah Azmi, and Rizalman Mamat. 2021. “Experimental Investigation of Thermo-Physical Properties of Tri-Hybrid Nanoparticles in Water-Ethylene Glycol Mixture.” Walailak Journal of Science and Technology 18(8).

Sarntichartsak, Pongsakorn, and Sirichai Thepa. 2013. “Modeling and Experimental Study on the Performance of an Inverter Air Conditioner Using R-410A with Evaporatively Cooled Condenser.” Applied Thermal Engineering 51(1–2): 597–610. http://dx.doi.org/10.1016/j.applthermaleng.2012.08.063.

Setiyo, Muji, Sudjito Soeparman, Nurkholis Hamidi, and Slamet Wahyudi. 2017. “Caractéristiques de l’effet Refroidissant d’un Système Frigorifique à Demi-Cycle Sur Un Système Au GPL.” International Journal of Refrigeration 82: 227–37. http://dx.doi.org/10.1016/j.ijrefrig.2017.06.009.

Sukarman, Sukarman et al. 2019. “Energy Analysis Of Vapor-Compression Refrigeration ( VCR ) System.” International Journal of Scientific & Technology 8(09): 1285–89.

Sukarman, Sukarman, Amri Abdullah, and R. Hengki Rahmanto. 2019. “Analisis Kinerja Mesin Pendingin Kompresi Uap Menggunakan HFC-236fa Sebagai Alternatif Pengganti R-22.” JTERA (Jurnal Teknologi Rekayasa) 4(1): 131.

Taib, M. Y, A. A Aziz, and A. B. S Alias. 2010. “Performance Analysis Of A Domestic Refrigerator.” In 1st NCMER 2010, 26-27 May, 2010, , 582–91. http://umpir.ump.edu.my/1593/.

UNEP. 2007. Decisions Adopted by the Nineteenth Meeting of the Parties to the Montreal Protocol on Substances That Deplete the Ozone Layer. Nairobi, Kenya: United Nations Environment Programme (UNEP) Ozone Secretariat;

W. F, Stoecker. 2005. Refrigersi Dan Pengkondisian Udara. Jakarta: Erlangga.

Wang, S. K. 2000. Handbook of Air Conditioning and Refrigeration. McGraw-Hill.

Wang, Zanxin, Fangyuan Zheng, and Shiya Xue. 2019. “The Economic Feasibility of the Valorization of Water Hyacinth for Bioethanol Production.” Sustainability (Switzerland) 11(3).

World Meteorological Organization. 2019. Scientific Assessment of Ozone Depletion: 2018. https://ozone.unep.org/sites/default/files/2019-05/SAP-2018-Assessment-report.pdf.

Yashar, D. A., S. Lee, and P. A. Domanski. 2015. “Rooftop Air-Conditioning Unit Performance Improvement Using Refrigerant Circuitry Optimization.” Applied Thermal Engineering 83: 81–87. http://dx.doi.org/10.1016/j.applthermaleng.2015.03.012.




DOI: https://doi.org/10.24853/jurtek.14.1.127-138

Refbacks

  • There are currently no refbacks.


Jurnal Teknologi Indexed by:

Directory of Open Access JournalGoogle ScholarRoadIndonesia Scientific Journal Database (ISJD)Index Copernicus International (ICI)Garba Rujukan Digital(Garuda)CrossrefScience and Technology Index (SINTA)Directory of Research Journal Indexing (DRJI)CiteFactorResearchgateIndonesia One SearchAcedemia.eduResearchBibAcademickeysBielefeld Academic Search Engine (BASE)JifactorPKP IndexSherpa romeoworldcat


Copyright of Jurnal Teknologi (e-ISSN:2460-0288, p-ISSN:2085-1669).

 

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License

Powered by Puskom-UMJ